View
View
View
View
| Type of Product | Safety Guard Switching Unit |
| Model No | G9SX-GS226-T15-RT DC24 |
| Voltage | Residual voltage when ON: 3.0 or less (safety output, auxiliary output, external indicator output Reset input time (reset pressing time): 100ms V or more |
| Rated Voltage (V) | DC 24 |
Type of Product |
Safety Guard Switching Unit |
Model No |
G9SX-GS226-T15-RT DC24 |
Voltage |
Residual voltage when ON: 3.0 or less (safety output, auxiliary output, external indicator output Reset input time (reset pressing time): 100ms V or more |
Rated Voltage (V) |
DC 24 |
Monotaro ID |
39071347 |
Mass (g) |
About 240 |
Ambient Humidity to Use |
25 to 85%RH |
Response Time |
(ON → OFF) 15 ms or less |
Withstand voltage (V / min) |
Logical connection Input terminal ⇔ Power supply / other input / output terminals batch, all terminals batch ⇔ DIN rail: AC500 . |
Operating Time (ms) |
(OFF → ON) When safety input is ON: 50 or less, when logical connection input is ON: 100 or less |
Function |
Safety guard switching unit |
Vibration Resistance |
10 Hz 55 - 10 Single amplitude 0.375 mm (Double amplitude 0.75 mm) |
Terminal Block |
Screw terminal block |
Output Configuration |
(Safety instantaneous output) 2 outputs, (Safety off-delay output) 2 outputs, (Auxiliary output) 6 outputs |
Wiring Length |
100m or less (for safety input and logic connection input) (External connection impedance: 100Ω or less and 10nF or less) |
Leakage Current (mA) |
OFF: 0.1 or less (safety output, auxiliary output), 1 or less (external indicator light output) |
Shock Resistance |
300 m/s² |
Country of Origin |
CHINA |
Import Country |
Direct Import from Japan |
Name of Manufacturer/Packer/Importer |
Omron Corporation |
Operation Ambient Temperature (°C) |
-10 to +55 (with no icing or condensation) |
Insulation Resistance (MOhm) |
Logic connection input terminal ⇔ Power supply, other I / O terminals, all terminals ⇔ Between DIN rails: 20 or more DC100V Mega |
Tightening Strength |
(Terminal) 0.5 Nm |
Maximum Set Time (Seconds) |
Off-delay time: 15 |
Mode Switching (ms) |
Mode switching input switching allowable time: 450 or less Operation mode switching response time: 50 or less |