Monitors: Phase loss, Phase unbalance, Phase sequence, Overload trip current, Under / Over current in 3Ø motors. Accuracy : 5% of set value. 2 C/O output relay. Auto / Remote test available. MPCT range : 10A - 80A Earth Fault Current Measurement with EFCT : 1A to 160A Aux supply : 90 - 270V AC / DC Time Setting :- Over Current Trip Time: 0 - 999sec, Under Current Ranges : Start With OFF then 1A TO 79A, Of IR (Rated Current) Step Size : 1A, Under Current Trip Time: 0 - 999sec Current Asymmetry Ranges : Start With OFF then 1A TO (Ir-1)A, Of IR (Rated Current) Step Size : 1A, Current Asymmetry Trip time: 0 - 999sec, Locked current / Stall current: (Ir+1)A to 60A(Default :20A), (Ir+1)A to 240A(Default : 80A), (Ir+1)A to 480A(Default: 160A) Step Size : 1A, Locked Current Trip time: 0 - 999sec, Earth Fault Ranges : Start With OFF then 1A TO 160A, Step Size : 1%, Earth Fault Trip time: 0 - 999sec, Phase Loss trip time: Instantaneous, Phase Reversal Trip time: Instantaneous Functional Specifications :- Over Load NEMA class : Start with OFF then Curve 5, 10, 15, 20, 30Over Current, Ranges : Start With OFF then 4A TO 480AOf IR (Rated Current)Step Size : 1A Measuring Parameter :-Monitors Over Load (As per NEMA Curve), Over Current, Under Current, Earth Fault, Lock Current, Current Asymmetry, Phase Sequence, Phase Failure Current Measuring Range :-3A - 80A (via external MPCT)