View
View
View
View
| Accuracy | ±1.5%rdg±8dgt, ±1.5%rdg±4dgt, ±1.5%rdg±4dgt, [Ground voltage measurement] ±2.3%rdg±8dgt (50Hz/60Hz), ±1.3%rdg±4dgt (DC) |
| Measurement Method | Two-electrode method (compatible with Class D measurements) / Three-electrode method (compatible with Class A to D measurements) |
| Voltage | Tolerance: 25Vrms |
| Type of Product | Earth Resistance Meter |
Accuracy |
±1.5%rdg±8dgt, ±1.5%rdg±4dgt, ±1.5%rdg±4dgt, [Ground voltage measurement] ±2.3%rdg±8dgt (50Hz/60Hz), ±1.3%rdg±4dgt (DC) |
Measurement Method |
Two-electrode method (compatible with Class D measurements) / Three-electrode method (compatible with Class A to D measurements) |
Voltage |
Tolerance: 25Vrms |
Type of Product |
Earth Resistance Meter |
Model No |
FT6031-50 |
Measuring Current |
3 electrode method: 25 mArms or less, 2 electrode method: 4 mArms or less |
Function |
Live line warning display, zero adjustment, continuous measurement mode, wireless communication (only when Z3210 is installed), comparator |
Measurement Range |
20Ω(0 to 20Ω), 200Ω(0 to 200Ω), 2000Ω(0 to 2000Ω), [Accuracy] 0-20 Ω: ±1.5%rdg±8dgt, 0 Ω-200 Ω: ±1.5%rdg±4dgt, 0 Ω-2000 Ω: ±1.5%rdg±4dgt |
Power Supply |
Requires 4 x AA alkaline batteries (LR6), Number of measurements possible: 500 (Measurement conditions: 3-electrode method, 10Ω measurement at 10-second intervals, Z3210 not installed) |
Part No |
64-4013-32 |
Country of Origin |
Japan |
Monotaro ID |
63634498 |
Measuring Time |
3 electrode method: within 6; 2 Sec electrode method: within 3 Sec |
Name of Manufacturer/Packer/Importer |
HIOKI E.E. CORPORATION |
Import Country |
Direct Import from Japan |
Mass (g) |
570 (including battery and protector, excluding terminal cover and other accessories) |
Applicable Standard |
Safety Main unit / Measurement circuit: EN61010, EMC: EN61326, Ground resistance meter: EN61557 |
RoHS Directive |
Correspondence |
Resistance (kΩ) |
Auxiliary installation electrode tolerance: 50 |
Specifications |
Drop proof: 1m above concrete (with protector attached) |
Dimension (WxDxH) |
185x111x44 mm |
Operating Temperature / Humidity Range |
-25 to 40°C, 90% rh or less (non-condensing), relative humidity below 25% rh at 40 to 65°C (non-condensing) |
Frequency Measurement Range (Hz) |
128±2 |
Under Voltage |
Measurement: 0–30Vrms |
Where to Use |
Indoor, outdoor (excluding farm), pollution degree 3, altitude up to 2000m |
Dust/Water Protection |
Dustproof performance: IP6x, waterproof performance: IPx5 / IPx7, (EN60529) |
Storage Temperature/Humidity Range |
-25 to 65°C, 80% RH or less (non-condensing) |
Looking for bulk pricing or different specifications?