View
View
View
View
| Type of Product | Power Transducer |
| Model No | PTD-1 |
| Monotaro ID | 62905998 |
| Mass (g) | (Body) 230, (CT included) 77 |
Type of Product |
Power Transducer |
Model No |
PTD-1 |
Monotaro ID |
62905998 |
Mass (g) |
(Body) 230, (CT included) 77 |
Operation Environment |
-20 ℃ to + 50 ℃, 85% RH or less ・ No condensation |
Insulation Resistance |
500 VDC, 100 MΩ or more (between power supply terminals and output terminals) |
Withstand Voltage |
2000 VAC (50/60 Hz), 1 min (between power supply terminals and output terminals) |
Voltage |
Single phase 100V / 200V |
Frequency (Hz) |
50/60 |
Country of Origin |
Japan |
Import Country |
Direct Import from Japan |
Output Voltage |
0 to 5VDC / 0 to rated power |
Included Components |
Compact clamp type AC current sensor (CTT-16-CLS) |
Screw Tightening Torque (Nm) |
(M4)0.7, (M3)0.3 |
Overall Accuracy |
± 2% FS (50 / 60Hz sine wave current power factor 1) |
Measurement Range |
(Maximum) 0 to 10VDC / 0 to 200% of rated power (however, the through current must not exceed 100A) |
Name of Manufacturer/Packer/Importer |
URD Co., Ltd. |
Ripple Wave (mVp-p) |
100 |
Specifications |
(CT sensitivity setting) The sum of the current values at the ON position of the front panel surface, 1A to 4A, 10A to 40A, 8-digit DIP switch is the rated current sensitivity. However, 100A must not be exceeded, (Rated power calculation method) P = E ・ I (W), output 5V |
Circuit System |
2-wire (50 / 60Hz) |
Responsiveness |
Output setting time at 0 to 100% load: within 0.5s |
Auxiliary Power |
± 15V / ± 10% Allowable current 50mA or less (Can be used for external system) |