View
View
View
View
| Storage Temperature | -20 To 60°C (No Freezing) |
| Type of Product | EB3C type relay barrier (intrinsically safe explosion-proof structure) |
| Model No | EB3C-R16CDN |
| Mass (g) | About 390 |
Storage Temperature |
-20 To 60°C (No Freezing) |
Type of Product |
EB3C type relay barrier (intrinsically safe explosion-proof structure) |
Model No |
EB3C-R16CDN |
Mass (g) |
About 390 |
Contact Configuration |
1A |
Rated Voltage (V) |
DC24 |
Contact Resistance |
50 mΩ or Less (Initial Value) |
Power Consumption (W) |
4.8 |
Monotaro ID |
47999195 |
Rated Insulation Voltage (V) |
AC250 V, DC125 V(UL:AC125 V, DC24 V)[Ui] |
Power Supply Voltage |
DC24 V |
Country of Origin |
Japan |
Short Circuit Protection |
None |
Import Country |
Direct Import from Japan |
Protection Class |
IP20(IEC60529) |
Connecting Terminal |
M3 screw terminal |
Name of Manufacturer/Packer/Importer |
IDEC Corporation |
Operation Ambient Temperature (°C) |
-20 To 60°C (No Freezing) |
Insulation_Resistance (MΩ) |
10 MΩ or more (DC500V mega, applied at the same voltage resistance point) |
Return Time |
[Relay output] 10 ms or less (rated power supply voltage), [Transistor output] 0.4 ms or less (Typ.) (resistive load) |
Specifications |
Non-Intrinsically Safe Circuit Connection Type: Terminal Connectionnon-Intrinsically Safe Circuit Type: Relay Outputmaximum Non-Intrinsically Safe Circuit Voltage (Um): 250V (Ul: 125V)Maximum External Capacitance (Co): When Channel Is Wired Separately: 470Nf, When Channel Is Wired Commonly: 490Nfmaximum External Resistance (Rc): When Channel Is Wired Separately: 300Ω, When Channel Is Wired Commonly: 600/(N+1)Ω (N = Number Of Channel Commons)Permissible Fluctuation Rate: ±10% |
Output Current (mA) |
[Io] Channel separate wiring: 14.2, Channel common wiring: 227.2 (max) |
Barometric Pressure (hPa) |
800 - 1100 |
Type of Terminal Fitting |
35mm wide DIN rail or panel direct mounting (M4 screw) |
No. of Storage |
Circuits: 16 |