Model No
View
View
View
View
| Storage Temperature | -25 to 65℃ |
| Type of Product | Motor Relay |
| Model No | SE-KQ2AN |
| Mass (g) | Approximately 170 to 230 |
Storage Temperature |
-25 to 65℃ |
Type of Product |
Motor Relay |
Model No |
SE-KQ2AN |
Mass (g) |
Approximately 170 to 230 |
Operating Temperature Range |
-10 to 60 ℃ (no icing) |
Contact Configuration |
1C |
Rated Voltage (V) |
(Motor circuit) AC500 or less (three-phase) [Set-3□ Current converter primary voltage], (Control power circuit) AC100/110/120, AC200/220/240, AC380/400/440 (three-phase) [single-phase voltage if reverse phase protection is not required] |
Shock Resistance |
294 m/s² X, Y, Z Directions |
Withstand Voltage |
Between electrical circuit and mounting panel: AC2000V 1 min, Between contact circuit and other circuits: AC2000V 1 min, Contact gap: AC 1000 V 1 min |
Monotaro ID |
46657335 |
Power Consumption (VA) |
About 7 |
Frequency (Hz) |
50/60 (allowable fluctuation range: ± 5% of rated frequency) |
Operating Time |
Overload element: ・0.5s or less at an overcurrent of 140% of the current setting value Overload element (startup lock time): ・Operation at a current of approximately 30% or more of the current setting value Scale magnification x 1: 1 to 10s (limited time), Operation scale magnification x 4: 4 to 40s (limited time), Phase loss element: High sensitivity setting (H): 2s or less; Low sensitivity setting (L): 3±1s (operating time when the current at the time of one complete phase loss is equal to the current setting value), Reverse phase element: 0.5 seconds or less (operation time in a reverse phase voltage state equal to the rated voltage), Setting error of overload element (startup lock time): Time setting scale 1: +10%, -5% of maximum setting value Time setting scale 2 to 10: ±10% of maximum setting value, Effect of temperature on overload element (start-up lock time): ±10% (at 0 to 40°C) ±20% (at -10 to +50°C), Effect of overload element frequency (startup lock time): ±5% (at ±5% change of rated frequency), Effect of the control power supply for overload elements (startup lock time): ±5% (at +10% and -15% change of rated voltage) |
Rated Current (A) |
1 to 80 or 64 to 160 (three-phase) [SET-3 * Current converter primary current] |
Protective Function |
Overload, open phase, anti-phase protection (3E relay) |
Country of Origin |
Japan |
Import Country |
Direct Import from Japan |
Vibration Resistance (Destruction) |
10 to 25Hz 2 mm double amplitude 2h each for X, Y, Z directions |
Name of Manufacturer/Packer/Importer |
Omron Corporation |
Case Color |
Munsell 5Y7/1 |
Overload Withstand |
(Motor circuit) 20 times the current setting value, 2 seconds, 2 times (1 minute interval) [Primary current of SET-3□ current converter], Continuous current: 125% of the maximum setting current value of each current setting range, (Control power circuit) 1.15 times the rated voltage, 3 hours, 1 time |
Insulation Resistance (MOhm) |
Between all electrical circuits and mounting panel: 10 or more Between contact circuits and other circuits and between contact poles: 5 or more |
Allowable Fluctuation of Voltage |
(Control power circuit) 10% or -15% of the rated voltage (however, 10% or -50% for manually resettable open-phase elements) |
Case Type |
Panel mount type |
Operating Patterns |
Start-up lock and instantaneous operation characteristics |
Looking for bulk pricing or different specifications?