View
View
View
View
| Basic Accuracy | Voltage: ±0.1% of nominal voltage, Current: ±0.1%rdg ±0.1%fs + current sensor accuracy, Active power: ±0.2%rdg ±0.1%fs + current sensor accuracy |
| Measurement Functions | 1. Transient voltage: Calculated from 1 waveform using 2MHz sampling/2 frequency waves (200kHz sampling) / 3. Voltage 1/2 RMS value: Calculated for each waveform with a half-wave shift / Current 1/2 RMS value: Calculated for each half-wave / 4. Swell, dip, momentary power interruption: Detected using voltage 1/2 RMS value / 5. Inrush current: Detected using current 1/2 RMS value / 6. Voltage waveform comparison: Comparison by automatically generating a judgment area / 7. Instantaneous flicker value: According to IEC61000-4-15 / 8. Frequency 200ms: Calculated from 10 or 12 waves (40-70Hz) / 9. Frequency 10 seconds: Calculated from a 10-second waveform |
| Current Range | AC 500mA to 5kA (measurement range varies depending on the sensor used) |
| Power Range | 300W to 3MW (automatically determined by the voltage and current range used) |
Basic Accuracy |
Voltage: ±0.1% of nominal voltage, Current: ±0.1%rdg ±0.1%fs + current sensor accuracy, Active power: ±0.2%rdg ±0.1%fs + current sensor accuracy |
Measurement Functions |
1. Transient voltage: Calculated from 1 waveform using 2MHz sampling/2 frequency waves (200kHz sampling) / 3. Voltage 1/2 RMS value: Calculated for each waveform with a half-wave shift / Current 1/2 RMS value: Calculated for each half-wave / 4. Swell, dip, momentary power interruption: Detected using voltage 1/2 RMS value / 5. Inrush current: Detected using current 1/2 RMS value / 6. Voltage waveform comparison: Comparison by automatically generating a judgment area / 7. Instantaneous flicker value: According to IEC61000-4-15 / 8. Frequency 200ms: Calculated from 10 or 12 waves (40-70Hz) / 9. Frequency 10 seconds: Calculated from a 10-second waveform |
Current Range |
AC 500mA to 5kA (measurement range varies depending on the sensor used) |
Power Range |
300W to 3MW (automatically determined by the voltage and current range used) |
Power Supply |
AC adapter Z1002 (100-240V, rated 17A, 50/60Hz), battery pack Z1003 (continuous use time 180 minutes, charges via AC adapter connection, charging time 5 hours 30 minutes) |
Display |
6.5-inch TFT color LCD+ (640 x 480 dots) |
Type of Product |
Power Storage Analyzer |
Interface |
SD/SDHC memory card, LAN+ (HTTP server function/FTP function), USB+2.0+ (communication) |
Calibration Certificate |
General calibration |
Model No |
PQ3198-94 |
No. of Channels |
4 |
Country of Origin |
Japan |
Included Components |
Instruction manual x 1, Measurement guide x 1, Voltage cord L1000 x 1 (red, yellow, blue, gray, black x 4, alligator clips x 8), Spiral tube x 20, Color clips, AC adapter Z1002 x 1, Strap x 1, USB cable (1m) x 1, Battery pack Z1003 x 1, SD memory card 2GB Z4001 x 1 |
Monotaro ID |
29104917 |
Name of Manufacturer/Packer/Importer |
HIOKI E.E. CORPORATION |
Import Country |
Direct Import from Japan |
Specifications |
[Voltage Range] ch1-3: Voltage measurement 600.00Vrms, transient measurement 6.0000kVpeak / ch4: 600.00Vrms or DC, transient measurement 6.0000kVpeak |
Dimension (WxDxH) |
300x211x68 mm |
Mass (Kg) |
2.6 (including battery pack Z1003) |
Measuring Time |
In addition to single-phase 2-wire/single-phase 3-wire/three-phase 3-wire/three-phase 4-wire systems, a separate channel 4 allows for voltage/current/power measurement (DC or AC). |
RoHS Directive |
Correspondence |
Set Contents |
PQ3198+x1, AC+flexible current sensor CT7045+x4, carrying case +C1009+x1, branch code +L1021-02+x3 |
Recording |
Maximum duration/repeatable ON: 1 year, maximum recorded events: 9999 x 366 days (up to 9999 events per day), Repeatable OFF: 35 days, maximum recorded events: 9999 events |