View
View
View
View
| Weight | 46 g |
| Type of Product | Pressure sensor |
| Part No | 8035535 |
| Accuracy | 1.5 %FS |
Weight |
46 g |
Type of Product |
Pressure sensor |
Part No |
8035535 |
Accuracy |
1.5 %FS |
Connection Type |
Plug |
Country of Origin |
Germany |
Mounting Type |
Front panel mountingWith threadVia wall/surface bracket |
Housing Material |
Reinforced Pa |
Ambient Temperature |
0 °C - 50 °C |
Display Type |
Illuminated LCD |
Name of Manufacturer/Packer/Importer |
D.K. DIES AND TOOLS |
Analogue Outputs |
0 - 10 V4 - 20 mA1 - 5 V |
Symbol |
995685 |
Note on Materials |
RoHS compliant |
Contact Material |
Fluoro rubber High-alloy stainless steel |
Variable Align System |
Relative pressure |
Ukca Marking |
To UK instructions for EMCTo UK RoHS instructions |
Mounting position |
Any |
Operating Medium |
Compressed air to ISO 8573-1:2010 [7:4:4]Inert gas |
End Value |
-0.1 MPa |
Cleanroom Suitability Measured According To ISO 14644-14 |
Class 4 according to ISO 14644-1 |
Connector Systems |
Plug pattern L1J |
Protection Against Tampering |
IO-Link PIN code |
Media Temperature |
0 °C - 50 °C |
Core |
4 |
Overload Pressure |
0.5 MPa |
Setting Range Hysteresis |
0 % - 90 % |
Labs (Pwis) Conformity |
VDMA24364-B1/B2-L |
Item Code |
SPAN-V1R-G18M-PNLK-PNVBA-L1 |
Temperature coefficient |
0.05 %FS/K |
Pneumatic Connection |
Male thread G1/8Female thread M5 |
Reverse Polarity Protection |
For all electrical connections |
Switching Element |
NC or NO, switchable |
Note on Operating and Pilot Medium |
Lubricated operation possible |
Protection Degree |
IP40 |
Corrosion Resistance Class crc |
2 - Moderate corrosion stress |
Measurement Method |
Piezoresistive pressure sensor |
Setting Option |
IO-Link Teach-in Via display and buttons |
Start Value |
0 MPa |
CE |
To EU EMC DirectiveIn accordance with EU RoHS Directive |
Approval |
RCMc UL us - Listed (Oil) |
Electrical Connection 1 Connection Pattern |
00995428 |
Repetition Accuracy |
0.3 %FS |
Setting Range Threshold Value |
0 % - 100 % |
Operational Voltage |
15 V - 30 V |
Displayable Units |
MPabarinH2OinHgkPakgf/cm²mbarmmHgpsi |
Short Circuit Current Rating |
Yes |
IO-Link Process Data Content In |
14 bit PDV (pressure measurement value)2 bit BDC (pressure monitoring) |
IO-Link Sio-Mode Support |
Yes |
Load Resistance Current Output |
500 Ohm |
IO-Link Profile |
Smart sensor profile |
IO-Link Process Data Length Out |
0 bytes |
Protocol |
IO-Link |
IO-Link Protocol Version |
Device V 1.1 |
Io-Link Min. Cycle Time |
3 ms |
IO-Link Port Class |
A |
IO-Link Function Classes |
Binary data channel (BDC)Process data variable (PDV)IdentificationDiagnosticsTeach channel |
IO-Link Data Storage Required |
500 Byte |
IO-Link Communication Mode |
COM2 (38.4 kBaud) |
Load Resistance Voltage Output |
20 kOhm |
Certification |
UL E322346 |
Suitability For The Production of Li-Ion Batteries |
Suitable for battery production with reduced Cu/Zn/Ni values (F1a) |
Looking for bulk pricing or different specifications?