| Type of Product | Comprehensive Tester |
| Model No | KEW6024PV |
| Country of Origin | Japan |
| Name of Manufacturer/Packer/Importer | Kyoritsu Electrical Instruments Co., Ltd. |
Type of Product |
Comprehensive Tester |
Model No |
KEW6024PV |
Country of Origin |
Japan |
Name of Manufacturer/Packer/Importer |
Kyoritsu Electrical Instruments Co., Ltd. |
Import Country |
Direct Import from Japan |
Monotaro ID |
29968128 |
Mass (g) |
Approximately 900 (including batteries) |
Included Components |
Measuring probe with remote switch (7196A), alligator cord set (7244A), tip bracket / long (8017), tip bracket / standard (8072), USB adapter + KEWReport / software (8212-USB), shoulder belt / cord belt (9155), Carrying case (9156), AA alkaline battery (LR6) x 6, Instruction manual |
Suitable Battery |
AA alkaline battery LR6 x 6 |
Measurement Range |
[Insulation resistance meter] First effective range/insulation resistance measurement: (250V) 1.51-100MΩ, (500V) 1.51-200MΩ, (1000V) 1.51-1000MΩ, Second effective range: (250V) 1.20-1.50MΩ/100.1-2000MΩ, (500V) 1.20-1.50MΩ/200.1-2000MΩ, (1000V) 1.20-1.50MΩ/1001-2000MΩ [Voltmeter] AC5-600V (45-65Hz) DC25-1000V, (Earth resistance meter) 20/200/2000Ω: Simple measurement, precision measurement |
Applicable Standard |
IEC 61010-1 CAT III 600V, CAT IV 300V Pollution Degree 2, IEC 61010-2-030, IEC 61010-031, IEC 60529 (IP54), IEC 61557-1, -2, -5, -10, IEC 61326-1, 2-2, JIS C1302 compliant (insulation resistance meter), JEM-TR228BU15001 |
Circuit Voltage |
(Open) 1.2 times or less of the rated measured voltage value |
RoHS Directive |
Correspondence |
Dimensions, Length L x Width W x Depth D (mm) |
84x184x133 |
Measuring Current |
Insulation resistance measurement/lower limit measurement resistance value: 1 to 1.2mA, (250V) 0.25MΩ, (500V) 0.5MΩ, (1000V) 1MΩ |
Measurement Voltage (V) |
(PV insulation resistance measurement) 500/1000, (insulation resistance measurement) 250/500/1000 |
Accuracy |
(PV insulation resistance measurement) 1.5% rdg 5dgt, 5.0% rdg 6dgt, (Insulation resistance measurement) 1st effective range / 1.5% rdg 5dgt, 2nd effective range / 5.0% rdg 6dgt, ( Ground resistance meter) 3.0% rdg 0.1Ω / 20Ω, 3.0% rdg 3dgt: 200 / 2000Ω, (voltmeter) 1.0% rdg 4dgt |
Short Circuit Current |
DC1.5 mA or less |
Power Supply |
AA alkaline battery LR6 x 6 |
Dimension (WxDxH) |
184x84x133 mm |
Voltage (Dc) |
±5 to 1000 V |
Length (mm) |
133 |
AC Voltage (Volts) |
5 to 600(45 to 65Hz) |
Effective maximum display value |
(Auto Range) 20/200/2000MΩ |