View
View
View
View
| Rated Current (A) | 50 |
| Type of Product | Compact Breaker |
| No. of Pole | 3P3E |
| Model No | BSH35035 |
Rated Current (A) |
50 |
Type of Product |
Compact Breaker |
No. of Pole |
3P3E |
Model No |
BSH35035 |
Material |
Case / PET resin, handle / PBT resin, contacts / silver alloy, terminal board / copper alloy |
Standard |
Electrical Appliance and Material Safety Law, Japanese Industrial Standards JIS C8211 |
Mechanical Durability |
40 thousand times |
Operating Voltage |
(Overvoltage) 130 ± 5 |
Country of Origin |
Japan |
Name of Manufacturer/Packer/Importer |
Panasonic Corporation |
Monotaro ID |
46718474 |
Rated Breaking Capacity (kA) |
2.5 |
Rated Voltage (V) |
AC100 / 200 only |
Import Country |
Direct Import from Japan |
Terminal Shape |
Power supply side: Plug-in terminal (plug-in type) Compatible bar size t2mm, Load side: Crimp terminal dedicated screw terminal M5 |
Overcurrent Tripper Type |
Thermodynamic Electromagnetic |
Mass (Kg) |
About 0.18 |
Operating Time |
(Overvoltage) Within 0.5 Seconds (Reverse Connection Possible) |
Tightening Torque (Nm) |
2.0-2.5 |
Specifications |
[General structure] Operating mechanism / trip-free type quick disconnect toggle mechanism that does not require reset operation, [Performance and functions] Overcurrent performance / Does not automatically shut off when a current equal to the rated current is applied with a tungsten bulb load. The contacts do not weld. Switching performance / current of 6 times the rated current, 35 times with manual shutoff, 15 times with automatic shutoff + 50 times in total, temperature rise of each part / power supply terminal part: 60 ° C or less (plug-in terminal), load terminal part: 60 ° C or less (screw terminal), contact part: 100 ° C or less, terminal performance / power supply side plug-in terminal: 5 times or less |
Insulation Resistance (MOhm) |
5 or more |
Electrical Durability for Opening and Closing |
6000 times |
Vibration Resistance |
Vibration frequency 16.7Hzxvibration displacement acceleration 19.6 m/s²xcompound amplitude 4 mmx1 hour, the circuit breaker will not open and no abnormality will occur in any part. |
Ambient Humidity (% RH) |
45-85 |
Operation Ambient Temperature (°C) |
-10 to 50 (however, the rate of reduction of the rated current depending on the ambient temperature is based on the temperature correction table.) |
Shock Resistance |
No damage to the components in the impact acceleration 490 m / s 2. |