View
View
View
View
| Storage Temperature | -25 to 65℃ (no condensation or freezing) |
| Type of Product | Temperature Controller |
| Input Type | Full multi input |
| Display Type | 11 segment digital display and single emission display |
Storage Temperature |
-25 to 65℃ (no condensation or freezing) |
Type of Product |
Temperature Controller |
Input Type |
Full multi input |
Display Type |
11 segment digital display and single emission display |
Model No |
E5EC-CX4ABM-000 |
Control Output |
Linear current output (4 to 20 mA DC/0 to 20 mA DC, load 500Ω or less, resolution approximately 10000) |
Character Height (mm) |
PV:15.2, SV:7.1 |
Monotaro ID |
63699433 |
Power Supply Voltage |
AC100 to 240 50/60Hz |
Input Impedance |
Current input 150 or less, voltage input 1M or more (When connecting ES2-HB-N/THB-N, use a 1:1 connection.) |
No. Of Output |
4 (Auxiliary output 1 and 2 co mmon co mmon, auxiliary output 3 and 4 co mmon co mmon) |
Applicable Standard |
EN 61010-1(IEC 61010-1), RCM |
Shape |
DIN48x96 |
Terminal Shape |
Push-in Plus Terminal |
Country of Origin |
Japan |
Control |
ON/OFF or 2 degrees of freedom PID (with auto tuning) |
Import Country |
Direct Import from Japan |
Pattern Setting |
Digital setting with front keys |
Standard |
[Certification standards] cULus: UL 61010-1/CSA C22.2 No.61010-1, Korea Radio Regulations (Radio Act: KC mark) (some models only) |
Protection Class |
Front: IP66, Rear case: IP20, Terminal part: IP00 |
Operating Temperature Range |
-10 to 55℃ (no condensation or freezing) / 3-year warranty: -10 to 50℃ (no condensation or freezing) when installed as standard |
Name of Manufacturer/Packer/Importer |
Omron Corporation |
Pack of |
1 Pcs |
Specifications |
●Reco mmended fuse: T2A, AC250V time-lag low breaking capacity●Installation environment: Overvoltage category II, pollution degree 2 (EN/IEC/UL 61010-1)●[Effects of electromagnetic interference (according to EN 61326-1)] Thermocouple input (R, S, B, C/W, PLⅡ): (±1% of indicated value or ±10°C, whichever is greater) ±1 digit or less, other thermocouple input: (±1% of indicated value or ±4°C, whichever is greater) ±1 digit or less, platinum resistance thermometer input: (±1% of indicated value or ±2°C, whichever is greater) ±1 digit or less, analog input: ±1%FS ±1 digit or less, CT input: ±5%FS ±1 digit or less●Manual reset value: 0.0 to 100.0% (in 0.1% increments)●Configuration tool port: Top: Connect to the USB port on the PC side using the USB-serial conversion cable E58-CIFQ2. |
Other functions |
Manual output, heating/cooling control, loop break alarm function, SP lamp, alarm function, heater break detection function (including SSR failure), 40% AT, 100% AT, operation amount limit, input digital filter, robust tuning, PV input correction, protection, square root calculation function, operation amount change rate limit, simple calculation, temperature status display function, input moving average, display brightness setting |