Model No
View
View
View
View
| Type of Product | Motor Relay |
| Model No | K2CM-4L |
| Contact Configuration | 1A1B |
| Mounting | Surface mounting integrated type |
Type of Product |
Motor Relay |
Model No |
K2CM-4L |
Contact Configuration |
1A1B |
Mounting |
Surface mounting integrated type |
Mass (g) |
780 to 800 |
Withstand Voltage |
Withstand voltage AC2500V (between live terminal and mounting panel, between live terminals), AC 1000 V (contact interval) |
Monotaro ID |
46657037 |
Range |
(Current) 8 to 26A |
Import Country |
Direct Import from Japan |
Case Color |
Munsell 5Y7/1 |
Frequency Tolerance |
95 to 105% of rated frequency |
Overload Withstand |
Main circuit: 20 times the main circuit current setting, 2 seconds, 2 times, 1 minute intervals Control power circuit: 1.15 times the rated operating voltage, 3 hours, 1 time |
Series |
K2CM Series |
Operating Humidity Range |
35 to 85%Rh |
Influence of Voltage |
Overload: Operating value ±5%, operating time ±10%, Phase loss: Operating value ±5%, operating time ±10%, Reverse phase: Operating value ±5%, operating time ±10% |
Rated Working Voltage |
Motor circuit: AC200/220V, 400/440V, Output contact circuit: (contact 1a) AC120V/2A, AC240V/1A, AC440V/0.5A, DC110V/0.2A, DC220V/0.1A, (contact 1b) AC120V/5A, AC240V/2A, AC440V/1A, DC110V/0.2 A, DC220V/0.1A |
Allowable Fluctuation of Voltage |
(Control power circuit) 85 to 110% of the rated operating voltage. However, in the event of a phase loss, it must operate normally at 50% of the rated operating voltage. |
Detection Method |
(Reverse phase detection) Current reverse phase detection |
Country of Origin |
Japan |
Name of Manufacturer/Packer/Importer |
Omron Corporation |
Rated Insulation Voltage (V) |
Motor circuit: AC500, Control power circuit: AC500, Output contact circuit: AC500 |
Power Consumption (VA) |
Before operation (50 Hz): 3, during operation (50 Hz): 5 |
Operation Ambient Temperature (°C) |
-10 to 60 (no icing) |
Specifications |
●Test button operation (overload elements only): Operating time → time setting value, operating time setting characteristics, ±30%●Effect of waveform distortion: No malfunction with 100% content of each of the second to ninth harmonics (phase loss switch "low")●Phase loss: Operating value → 85% or less of current setting value (in a state of complete phase loss of one phase), operating time → 2s or less at current setting value (in a state of complete phase loss of one phase)●Reverse phase: Operating value → 50% or less of current setting value, operating time → 1s or less●Unbalance: Operating value → Maximum current phase is 85% or less of current setting value, operating unbalance rate: "high" 35±10% (25 to 45%), "low" 60% or more, unbalance rate = reverse phase/positive phase |
Insulation Resistance (MOhm) |
10 or more (between the live terminal and the mounting panel), 5 or more (between live terminals, between contact poles) |
Rated Frequency (Hz) |
50/60 |