Your Free Gift is Awaiting in your Inbox
Features |
|
Brand Name : | Schneider Electric |
Type of Product : | Multifunction Meter |
Model No : | METSEEM6400NGRSCL2 |
Accuracy Class : | 0.2 |
Voltage Measurement : | ±0.5% |
Current Measurement : | ±0.5% |
More Details |
-
Warranty
12 months manufacturer warranty -
100% Original
Products -
Free Shipping
on orders above Rs. 1,000 -
Secure
Payments -
100% buyer
Protection -
EARN
IB Coins -
7 days
Returnable
Current | Average line current of 3-phase, per-phase, and calculated neutral current |
Voltage | Average voltage of L-L, L-N parameters, and per-phase |
Frequency | Any available line |
Real, reactive, and apparent power | Total and per-phase value |
Displacement power factor | Average and per-phase signed, four-quadrant |
True power factor | Average and per-phase signed, four-quadrant |
Demand values
Current average | Present, Last, Predicted, Peak, and Peak Date Time |
Active power | Present, Last, Predicted, Peak, and Peak Date Time |
Reactive power | Present, Last, Predicted, Peak, and Peak Date Time |
Apparent power | Present, Last, Predicted, Peak, and Peak Date Time |
Demand sync methods | Thermal, Timed, Command Sync, and Clocked Sync |
Demand calculation mode | Sliding, fixed and rolling block |
Electrical characteristics
Type of measurement Measurement accuracy | True RMS, 64 samples per cycle |
Current, Phase | ±0.5% |
Voltage L-N, L-L | ±0.5% |
Power Factor | ±0.01 |
Power | ±0.5% |
Frequency | ±0.05% |
Real Energy | Class 0.5S and Class 0.2*1 as per IEC 62053-22 and Class 1.0 as per IEC 62053-21 for both CT nominal of 5 A and 1 A*2 |
Reactive Energy | IEC 62053-23 Class 2 |
THD and Individual Harmonic, V& A Input-voltage | Class 5.0 as per IEC 61557-12 for THD and individual harmonics up to 15th |
VT primary | 999 kV L-L max, starting voltage depends on VT ratio |
U nominal | 277 V L-N/480V L-L |
Measured V with full range | 35 to 600 VAC L-L |
Permanent overload | 750 VAC L-L |
Impedance | => 5 MO |
Frequency range | 50/60 Hz +/-5% |
VA burden | < 0.2 VAat 240 VAC L-N |
Input-current CT ratings | Primary adjustable 1 A to 32768 A Secondary 1A or 5 A l-nominal |
Measured Amps with over range & Crest Factor | 5mAto6A |
Withstand | Continuous 12 A, 50 A at 10 sec/hr |
Impedance | <0.3 MO |
Frequency range | 50/60 Hz +1-5% |
VA Burden AC control power | <0.1 VAat6A |
Operating range | 44- 277 VAC ±10% |
Burden | < 6 VA at 277 V L-N |
Frequency | 50/60 Hz nominal |
Ride-through time DC control power | 100 ms typical at 120 V AC and maximum burden 100 ms typical at 277 V AC and maximum burden |
Operating range | 44-277 V DC ±10% |
Burden | < 2 Wat 277 V DC |
Ride-through time Real time clock | 50 ms typical at 125 V DC and maximum burden |
Ride-through time Displays update | 3 years |
Instantaneous | 1 s |
Demand | 15s |
Harmonics | 5s |
Mechanical characteristics
Weight | ~600gms (21 oz) |
IP degree of protection | (IEC 60529) IP51 front display, IP30 meter body |
Material | Polycarbonate meets UL94V-0 flammability rating |
Dimensions Wx H x D | 96 x 96 x 73 mm (3.78 x 3.78 x 2.87 in) maximum (depth of the meter from housing mounting flange) and 13 mm (0.51 in) (protrusion of meter from housing flange) |
Mounting position | Vertical |
Panel thickness | 5 mm (0.196 in) maximum |
Operating temperature | Meter -10.. +60 °C (+14...+140 °F) |
Storage temperature | Meter -20...+70 °C (-4...+158 °F) |
Humidity rating | 5 to 95% RH at 50 °C (122 °F) (non-condensing) |
Pollution degree | 2 |
Altitude | 2000 m (6561 ft) Category III |
Product life | > 7 years |
EM6400NG multi-function meter display overview
A | Phase measurements | VL-N, VL-L, I, kVA, kW, kVAR, PF, VTHD, ITHD |
B | Demand measurements | DM, PrsDM, PrdDM, MD |
C | RTC | Date and time |
D | Negative indicator | |
E | Navigation key | To navigate down |
F | Energy readings | Apparent energy, Active energy, and Reactive energy |
G | Navigation key | To navigate up |
H | OK | Enter key |
I | Energy pulsing LED (Red), Heartbeat/communications LED (Green) | |
J | x 1000 indicator | |
K | System measurements | Vavg, kVA, F, lavg, kW, In, PFavg, kVAR, lunb |
L | Retainer clip | |
M | Input current terminals | A1 (S1, S2), A2 (S1, S2), A3 (S1, S2) |
N | RS-485 communications/ POP terminals | D1+, DO- |
O | Protective cover | |
P | Auxiliary power supply (control power) terminals | L+, N- |
Q | Input voltage terminals | V1, V2, V3, VN |
Buy Schneider Multi-Function Meter Accuracy 0.2 METSEEM6400NGRSCL2 online in India at wholesale rates. If you have been looking for Schneider Multi-Function Meter Accuracy 0.2 METSEEM6400NGRSCL2 dealers, your search ends here as you can get the best Schneider Multi-Function Meter Accuracy 0.2 METSEEM6400NGRSCL2 distributors in top cities such as Delhi NCR, Mumbai, Chennai, Bengaluru, Kolkata, Chennai, Pune, Jaipur, Hyderabad and Ahmedabad. You can purchase Schneider Multi-Function Meter Accuracy 0.2 METSEEM6400NGRSCL2 of the finest quality and rest assured to get the best in terms of both durability and performance. If you are bothered about the Schneider Multi-Function Meter Accuracy 0.2 METSEEM6400NGRSCL2 prices, you can be totally sure to get the best rates as Industrybuying brings you genuine Schneider Multi-Function Meter Accuracy 0.2 METSEEM6400NGRSCL2 rates and quality assured products only from the best of brands with exclusive brand discounts you won’t find anywhere else. Procure Schneider Multi-Function Meter Accuracy 0.2 METSEEM6400NGRSCL2 today and avail the best offers on your purchase.